Medusa: The 300-Node Beowulf
UWMLSC
>
Beowulf Systems
>
Medusa
Search the Medusa Web Pages
Links and Resources
- Frequently Asked Questions
- Bug Reporting
- CVS Archive
- UPS Status
- Ganglia Monitoring
- UWM LSC Group Computing
User Manual
- Backing Up Cron Jobs
- Becoming A User
- Connecting With Grid Tools
- LDAS Camp 2002
- LSC Grid Tools
- Obtaining LSC Grid Credentials
- Running Codes With Condor
Maintenance
- Adding A User
- Adding An LDAS User
- Bind Configuration
- Cloning A Node
- Data Recovery Procedure
- Documentation
- LDAS Administration
- Partitioning A Nodes Hard Disks
- Power Management
- Restoring A Database
- RPM Manual
- Scheduling LDAS DB Backup
- Slave Checklist
- Slave Work
Construction
- Benchmarking Results
- Benchmarking Software
- Channel Bonding
- Cluster-Dependencies
- Multimeter Instructions
- Node Prototype
- Paperwork
- Power Consumption
Design
- Bios Settings
- DHCP Configuration
- Fc3 Install
- File System
- Introduction
- IP Addresses
- Master Configuration
- Network Switch
- Physical Design
- Slave Configuration
- Software
Photo Gallery
- Hardware Pictures
- How To Take Pictures
- Setup Pictures
UPS Testing
Testing Results
Tests completed on 4-15-04
For all of the following tests the nodes are set to shutdown after 2 mins.
Test 1
Long power failure with idle nodes
The test effects 20 nodes
Clone nodes s001-s040
Pull ups power cable for nodes s001-s020
After all nodes shutdown plug ups cable back in.
Etherwake nodes. Make sure they all come back up.
Proper Result: All 20 nodes should shutdown cleanly and etherwake
Result: PASSED
3min 14sec for halt